Ultrasonic measurement Time-of-Flight Prosonic FMU30
Field of Application :
The FMU30 ultrasonic sensor is designed for continuous, non-contact level and flow measurement across various industrial applications. It is widely used in:
- Sewage treatment plants
- Process water tanks
- Loading, storage, and buffer tanks
Equipped with advanced software algorithms, the sensor provides real-time analysis and displays warning and alarm messages on a four-line plain text display. The envelope curve visualization ensures quick and accurate error diagnostics directly on-site.
Key Specifications :
- Process connection: Thread
- Temperature range: -20 to +60°C (-4 to +140°F)
- Pressure range: +0.7 to +3 bar (+10 to +44 psi)
- Maximum measuring distance:
- Sensor 1½": Liquids 5m (16ft), bulk solids 2m (6.6ft)
- Sensor 2": Liquids 8m (26ft), bulk solids 3.5m (11ft)
- Blocking distance:
- Sensor 1½": 0.25m (0.8ft)
- Sensor 2": 0.35m (1.15ft)
- International explosion protection certificates
Key Features & Benefits :
User-Friendly Operation
- Quick and simple commissioning via a menu-guided interface
- Four-line plain text display with 7 selectable languages for ease of use
Advanced Diagnostics & Monitoring
- Envelope curves displayed on-site for real-time diagnostics
- Integrated temperature sensor for automatic sound velocity correction
Versatile & Reliable Performance
- Linearization function (up to 32 points) enables conversion of measured values into length, volume, or flow rate
- Non-contact measurement minimizes service requirements
- Can be installed using G 1½ or 1½ NPT thread